3931
PoleDiscrepancy
Breaker Failure
ON
OFF
OFF
Pole Discrepancy supervision
3932
T-PoleDiscrep.
Breaker Failure
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay with pole discrepancy
4001
FCT TripSuperv.
TripCirc.Superv
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
TripCirc.Superv
1 .. 2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
TripCirc.Superv
1 .. 30 sec
2 sec
Delay Time for alarm
Addr.