Functions
2.7 Monitoring Function
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
142
1)
after three unsuccessful restarts, the device is taken out of service.
2)
DOK = „ Device OK“ = Break contact of the readiness relay = Life-contact
1 A/5 A-Setting
Jumper wrong 1/5 A
Indications:
Protection out of opera-
tion
„Error1A/5Awrong“
(192) „Error A/D-
conv.“ (181)
LED „ERROR“
DOK
drops out
Calibration data
Internal (EEPROM or RAM) Indication:
Using default values
„Alarm adjustm.“
(193)
As allocated
Earth current transform-
er sensitive/insensitivity
I/O-BG does not comply the
order number MLFB of the
device
Indications:
Protection out of opera-
tion
„Error neutralCT“
(194)„Error A/D-
conv.“ (181)
LED „ERROR“
DOK
drops out
Modules
Module does not comply
with ordering number
Indications:
Protection out of opera-
tion
„Error Board
BG1...7“ (FNo. 183
... 189)
and if applicable
„Error A/D-conv.“.
(181)
DOK
drops out
Current sum
Internal (measured value
acquisition)
Message
„Failure
Σ
I“ (162)
As allocated
Current Symmetry
External (power system or
current transformer)
Message
„Fail I balance“ (163) As allocated
Broken conductor
External (power system or
current transformer)
Message
„Fail Conductor“
(195)
As allocated
Voltage sum
Internal (measured value
acquisition)
Message
„Fail
Σ
U Ph-E“ (165) As allocated
Voltage Symmetry
External (power system or
voltage transformer)
Message
„Fail U balance“
(167)
As allocated
Voltage Phase Se-
quence
External (power system or
connection)
Message
„Fail Ph. Seq.“ (171) As allocated
Voltage failure, three-
phase „Fuse-Failure-
Monitor“
External (power system or
connection)
Message
Undervoltage protection
is blocked
„VT FuseFail>10s“
(169)
As allocated
Voltage failure, single
and two-phase „Fuse-
Failure-Monitor“
External (voltage transform-
ers)
Message
Undervoltage protection
is blocked
„VT FuseFail>10s“
(169)
As allocated
Voltage failure, three-
phase
External (power system or
connection)
Message
Undervoltage protection
is blocked
„Fail U absent“ (168) As allocated
Trip Circuit Monitoring
External (trip circuit or
control voltage)
Message
„FAIL: Trip cir.“
(6865)
As allocated
Monitoring
possible causes
Malfunction Re-
sponse
Message (F.No)
Device
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...