Time Synchronisation Interface
It is optionally possible to process 5 V, 12 V or 24 V time synchronization signals, provided that these are con-
nected to the inputs named in the following table.
Table 3-21
D-subminiature connector assignment of the time synchronization interface
1)
Assigned, but cannot be used
Fibre-optic Cables
WARNING!
Laser rays!
Do not look directly into the fiber-optic elements!
Signals transmitted via optical fibers are unaffected by interference. The fibers guarantee electrical isolation
between the connections. Transmit and receive connections are represented by symbols.
The character idle state for the optical fibre interface is „Light off“. If the character idle state is to be changed,
use the operating program DIGSI, as described in the SIPROTEC 4 System Description.
Further Connections
For further connections a visual inspection is sufficient for the time being. Electrical and functional controls are
performed during commissioning (see the following main section).
Pin No.
Designation
Signal meaning
1
P24_TSIG
Input 24 V
2
P5_TSIG
Input 5 V
3
M_TSIG
Return line
4
-
-
5
SHIELD
Shield potential
6
-
-
7
P12_TSIG
Input 12 V
8
P_TSYNC
Input 24 V
9
SHIELD
Shield potential
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...