Technical Data
4.1 General
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
232
4.1.4
Communication Interfaces
Operator Interface
Service / Modem Interface
AC
250 V
admissible current per contact ( continuous)
5 A
admissible current per contact (close and hold)
30 A for 0.5 s (NO contact)
Total current on common path
5 A continuous 30 A for 0.5 s
Operating time, approx.
8 ms
Alarm relay
with 1 NC contact or 1 NO contact
(switchable)
Switching Capability BRAKE
1000 W/VA
Switching capability OFF
30 W/VA
40 W resistive
25 W at L/R
≤
50 ms
Switching voltage
250 V
Permissible current per contact
5 A continuous
30 A for 0.5 s
Interference suppressions capacitors across relay
contacts
Ceramic, 4.7 nF, 250 V
Connection
Front side, non-isolated, RS232,
9-pin D-subminiature female connector for connection of a PC
Operation
With DIGSI
Transmission speed
Min. 4800 Baud; max. 115200 Baud;
Factory Setting: 38400 Baud; Parity: 8E1
Transmission distance
15 m / 50 feet
RS232/RS485
acc. to ordered version
Isolated interface for data transfer
Operation
with DIGSI
RS232/RS485
RS232/RS485 according to the ordering
variant
Connection for flush-mounted housing
Rear panel, slot „C“, 9-pin D-SUB female
connector
Shielded data cable
For panel surface mounted housing
In the housing on the case bottom;
9-pin D-subminiature female connector;
shielded data cable
Test Voltage
500 VAC
Transmission Speed
min. 4800 Baud; max. 115200 Baud
Factory setting 38400 Baud
RS232
Bridgeable distance
15 m / 50 feet
RS485
Bridgeable distance
1.000 m / 3280 feet / 0.62 miles
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...