Functions
2.1 General
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
41
Pre-fault and post-fault times will be included. If the binary input time is set for
∞
, then the length of the record
equals the time that the binary input is activated (static), or the
MAX. LENGTH
setting in address
410
, which-
ever is shorter.
2.1.6.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
2.1.6.4
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
402A
WAVEFORMTRIGGE
R
Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup
Waveform Capture
403A
WAVEFORM DATA
Fault event
Pow.Sys.Flt.
Fault event
Scope of Waveform Data
410
MAX. LENGTH
0.30 .. 5.00 sec
2.00 sec
Max. length of a Waveform
Capture Record
411
PRE. TRIG. TIME
0.05 .. 0.50 sec
0.25 sec
Captured Waveform Prior to
Trigger
412
POST REC. TIME
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after Event
415
BinIn CAPT.TIME
0.10 .. 5.00 sec;
∞
0.50 sec
Capture Time via Binary Input
No.
Information
Type of In-
formation
Comments
-
FltRecSta
IntSP
Fault Recording Start
4
>Trig.Wave.Cap.
SP
>Trigger Waveform Capture
30053
Fault rec. run.
OUT
Fault recording is running
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...