Functions
2.2 Automatic reclosure function (optional)
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
65
2.2.4
Information List
No.
Information
Type of In-
formation
Comments
2701
>AR on
SP
>AR: Switch on auto-reclose function
2702
>AR off
SP
>AR: Switch off auto-reclose function
2703
>AR block
SP
>AR: Block auto-reclose function
2711
>AR Start
SP
>External start of internal Auto reclose
2712
>Trip L1 AR
SP
>AR: External trip L1 for AR start
2713
>Trip L2 AR
SP
>AR: External trip L2 for AR start
2714
>Trip L3 AR
SP
>AR: External trip L3 for AR start
2715
>Trip 1pole AR
SP
>AR: External 1pole trip for AR start
2716
>Trip 3pole AR
SP
>AR: External 3pole trip for AR start
2727
>AR RemoteClose
SP
>AR: Remote Close signal
2731
>Sync.release
SP
>AR: Sync. release from ext. sync.-check
2737
>BLOCK 1pole AR
SP
>AR: Block 1pole AR-cycle
2738
>BLOCK 3pole AR
SP
>AR: Block 3pole AR-cycle
2739
>BLK 1phase AR
SP
>AR: Block 1phase-fault AR-cycle
2740
>BLK 2phase AR
SP
>AR: Block 2phase-fault AR-cycle
2741
>BLK 3phase AR
SP
>AR: Block 3phase-fault AR-cycle
2742
>BLK 1.AR-cycle
SP
>AR: Block 1st AR-cycle
2743
>BLK 2.AR-cycle
SP
>AR: Block 2nd AR-cycle
2744
>BLK 3.AR-cycle
SP
>AR: Block 3rd AR-cycle
2745
>BLK 4.-n. AR
SP
>AR: Block 4th and higher AR-cycles
2746
>Trip for AR
SP
>AR: External Trip for AR start
2747
>Pickup L1 AR
SP
>AR: External pickup L1 for AR start
2748
>Pickup L2 AR
SP
>AR: External pickup L2 for AR start
2749
>Pickup L3 AR
SP
>AR: External pickup L3 for AR start
2750
>Pickup 1ph AR
SP
>AR: External pickup 1phase for AR start
2751
>Pickup 2ph AR
SP
>AR: External pickup 2phase for AR start
2752
>Pickup 3ph AR
SP
>AR: External pickup 3phase for AR start
2781
AR off
OUT
AR: Auto-reclose is switched off
2782
AR on
IntSP
AR: Auto-reclose is switched on
2783
AR is blocked
OUT
AR: Auto-reclose is blocked
2784
AR not ready
OUT
AR: Auto-reclose is not ready
2787
CB not ready
OUT
AR: Circuit breaker not ready
2788
AR T-CBreadyExp
OUT
AR: CB ready monitoring window expired
2796
AR on/off BI
IntSP
AR: Auto-reclose ON/OFF via BI
2801
AR in progress
OUT
AR: Auto-reclose in progress
2809
AR T-Start Exp
OUT
AR: Start-signal monitoring time expired
2810
AR TdeadMax Exp
OUT
AR: Maximum dead time expired
2818
AR evolving Flt
OUT
AR: Evolving fault recognition
2820
AR Program1pole
OUT
AR is set to operate after 1p trip only
2821
AR Td. evol.Flt
OUT
AR dead time after evolving fault
2839
AR Tdead 1pTrip
OUT
AR dead time after 1pole trip running
2840
AR Tdead 3pTrip
OUT
AR dead time after 3pole trip running
2841
AR Tdead 1pFlt
OUT
AR dead time after 1phase fault running
2842
AR Tdead 2pFlt
OUT
AR dead time after 2phase fault running
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...