Functions
2.5 Distance Protection
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
180
Tripping logic
In the actual tripping logic, the output signals generated by the individual zones are combined to form the
output signals
„Dis.Gen. Trip“
,
„Dis.Trip 1pL1“
,
„Dis.Trip 1pL2“
,
„Dis.Trip 1pL3“
,
„Dis.Trip 3p“
. The single-pole information implies that only a single-pole tripping will take place. Further-
more, the zone that initiated the tripping is identified; if single-pole tripping is possible, this is also signalled as
shown in the zone logic diagrams (Figures 2-71 to 2-75). The actual generation of the commands for the trip-
ping (output) relay is executed within the tripping logic of the entire device.
2.5.4.2
Setting Notes
The trip delay times of the distance stages and intervention options which are also processed in the tripping
logic of the distance protection were already considered with the zone settings.
Further setting options which affect the tripping are described as part of the tripping logic of the device.