2.14 Instantaneous High-Current Switch-onto-Fault Protection (SOTF)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
294
2.14.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
2.14.4
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2401
FCT HS/SOTF-O/C
ON
OFF
ON
Inst. High Speed/SOTF-
O/C is
2404
I>>>
1A
0.10 .. 15.00 A;
∞
1.50 A
I>>> Pickup
5A
0.50 .. 75.00 A;
∞
7.50 A
2405A
I>>>>
1A
1.00 .. 25.00 A;
∞
∞
A
I>>>> Pickup
5A
5.00 .. 125.00 A;
∞
∞
A
2406
CBaux for I>>>
local only
local and rem.
local and rem.
CB-aux check for activa-
tion of I>>>
No.
Information
Type of In-
formation
Comments
4253
>BLOCK SOTF-O/C
SP
>BLOCK Instantaneous SOTF Overcurrent
4271
SOTF-O/C OFF
OUT
SOTF-O/C is switched OFF
4272
SOTF-O/C BLOCK
OUT
SOTF-O/C is BLOCKED
4273
SOTF-O/C ACTIVE
OUT
SOTF-O/C is ACTIVE
4281
SOTF-O/C PICKUP
OUT
SOTF-O/C PICKED UP
4282
SOF O/CpickupL1
OUT
SOTF-O/C Pickup L1
4283
SOF O/CpickupL2
OUT
SOTF-O/C Pickup L2
4284
SOF O/CpickupL3
OUT
SOTF-O/C Pickup L3
4285
I>>>>O/C p.upL1
OUT
High Speed-O/C Pickup I>>>> L1
4286
I>>>>O/C p.upL2
OUT
High Speed-O/C Pickup I>>>> L2
4287
I>>>>O/C p.upL3
OUT
High Speed-O/C Pickup I>>>> L3
4289
HS/SOF TRIP1pL1
OUT
High Speed/SOTF-O/C TRIP - Only L1
4290
HS/SOF TRIP1pL2
OUT
High Speed/SOTF-O/C TRIP - Only L2
4291
HS/SOF TRIP1pL3
OUT
High Speed/SOTF-O/C TRIP - Only L3
4292
HS/SOF TRIP 1p
OUT
High Speed/SOTF-O/C TRIP 1pole
4293
HS/SOF Gen.TRIP
OUT
High Speed/SOTF-O/C General TRIP
4294
HS/SOF TRIP 3p
OUT
High Speed/SOTF-O/C TRIP 3pole
4295
HS/SOF TRIPL123
OUT
High Speed/SOTF-O/C TRIP command L123