Functions
2.16 Backup Time Overcurrent Protection
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
304
Figure 2-153
Logic diagram of the
I
>> stage
1
)
Output indications associated with the pickup signals are listed in Table 2-12
2
)
Output indications associated with the trip signals are listed in Table 2-13
Definite time overcurrent stage
I
>
The logic of the overcurrent stages
I
> is structured identically to the
I
>> stages. In all references,
Iph>>
must
merely be replaced by
Iph>
or
3I0>> PICKUP
by
3I0>
. The parameter
2624
I> Telep/BI
is set to
NO
by
default. In all other respects, figure 2-153 applies.
Inverse time overcurrent stage
I
P
The logic of the inverse overcurrent stage also operates chiefly in the same way as the remaining stages. How-
ever, the time delay is calculated here based on the type of the set characteristic, the intensity of the current
and a time multiplier (following figure). A pre-selection of the available characteristics was already carried out
during the configuration of the protection functions. Furthermore, an additional constant time delay
T Ip Add