Functions
2.16 Backup Time Overcurrent Protection
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
308
For the tripping signals (table 2-13) the stage which caused the tripping is also output. If the device has the
option to trip single-pole, and if this option has been activated, the pole which has been tripped is also indicated
(refer also to Section 2.25.1„Tripping Logic of the Entire Device“).
Table 2-13
Trip signals of the indvidual phases
1)
If tripping by the 3I0 measuring unit is performed simultaneously with or after tripping by a phase measuring
unit and if 1-pole tripping is active, „O/C TRIP 1p.L1“, „O/C TRIP 1p.L2“ or „O/C TRIP 1p.L3“ is signalled.
2)
If tripping is only performed by the 3I0 measuring unit but not by a phase measuring unit, „O/C TRIP L123“
is signalled.
I
>>> PU L1
I
>>> PU L2
I
>>> PU L3
I
>>> PU E
„I-STUB PICKUP“
7201
(All pickups)
„O/C PICKUP“
7161
Internal indication
Display
Output indication
No.
I
>> PU L1
I
> PU L1
I
p PU L1
I
>>> PU L1
„O/C TRIP 1p.L1“ or „O/C TRIP L123“
7212 or
7215
I
>> PU L2
I
> PU L2
I
p PU L2
I
>>> PU L2
„O/C TRIP 1p.L2“ or „O/C TRIP L123“
7213 or
7215
I
>> PU L3
I
> PU L3
I
p PU L3
I
>>> PU L3
„O/C TRIP 1p.L3“ or „O/C TRIP L123“
7214 or
7215
I
>> PU E
I
> PU E
I
p PU E
I
>>> PU E
„O/C TRIP L123“
7215
I
>> PU L1
I
>> PU L2
I
>> PU L3
I
>> PU E
„O/C TRIP I>>“
7221
I
> PU L1
I
> PU L2
I
> PU L3
I
> PU E
„O/C TRIP I>“
7222
I
p PU L1
I
p PU L2
I
p PU L3
I
p PU E
„O/C TRIP Ip“
7223
I
>>> PU L1
I
>>> PU L2
I
>>> PU L3
I
>>> PU E
„I-STUB TRIP“
7235
(PU all)
„O/C TRIP“
7211
Internal Indication
Display
Output Indication
No.