Functions
2.19 Undervoltage and Overvoltage Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
372
2.19.3
Setting Notes
General
The voltage protection can only operate if, when configuring the device scope (address
137
), it has been set
to
Enabled
. Compounding is only available if (address
137
) is set to
Enabl. w. comp.
.
The overvoltage and undervoltage stages can detect phase-to-earth voltages, phase-to-phase voltages or the
positive sequence voltages; for overvoltage also the negative sequence voltage, zero-sequence voltage or a
different single-phase voltage can be used. Any combination is possible. Detection stages that are not required
are switched
OFF
.
Note
For overvoltage protection it is particularly important to observe the setting notes: NEVER set an overvoltage
stage (U
L-E
, U
L-L
, U
1
) lower than an undervoltage stage. This would put the device immediately into a state of
permanent pickup which cannot be reset by any measured value operation. As a result, operation of the device
would be impossible!
Phase-to-earth overvoltage
The phase voltage stages can be switched
ON
or
OFF
in address
3701
Uph-e>(>)
. In addition to this, you can
set
Alarm Only
, i.e. these stages operate and send alarms but do not generate any trip command. The setting
U>Alarm U>>Trip
creates in addition also a trip command only for the U>> stage.
The settings of the voltage threshold and the timer values depend on the type of application. To detect steady-
state overvoltages on long lines carrying no load, set the
Uph-e>
stage (address
3702
) to at least 5 % above
the maximum stationary phase-to-earth voltage expected during operation. Additionally, a high dropout to
pickup ratio is required (address
3709
Uph-e>(>) RESET
= presetting). This parameter can only be changed
in DIGSI at
Display Additional Settings
. The delay time
T Uph-e>
(address
3703
) should be a few seconds
so that overvoltages with short duration do not cause tripping.
The U
ph
>> stage (address
3704
) is provided for high overvoltages with short duration. Here an adequately high
pickup value is set, e.g. the 1
1
/
2
-fold of the nominal phase-to-earth voltage. 0.1 s to 0.2 s are sufficient for the
delay time
T Uph-e>>
(address
3705
).
Phase-to-phase overvoltage
Basically, the same considerations apply as for the phase voltage stages. These stages can be used instead
of the phase voltage stages or additionally. Depending on your choice, set address
3711
Uph-ph>(>)
to
ON
,
OFF
,
Alarm Only
or
U>Alarm U>>Trip
.
As phase-to-phase voltages are monitored, the phase-to-phase values are used for the settings
Uph-ph>
(ad-
dress
3712
) and
Uph-ph>>
(address
3714
).
For the delay times
T Uph-ph>
(address
3713
) and
T Uph-ph>>
(address
3715
) the same considerations
apply as above. The same is true for the dropout ratios (address
3719
Uphph>(>) RESET
). The latter setting
can only be altered in DIGSI at
Display Additional Settings
.