Functions
2.20 Frequency Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
386
2.20.4
Information List
3632
f4 PICKUP
45.50 .. 54.50 Hz
51.00 Hz
f4 Pickup
3633
f4 PICKUP
55.50 .. 64.50 Hz
62.00 Hz
f4 Pickup
3634
T f4
0.00 .. 600.00 sec
30.00 sec
T f4 Time Delay
No.
Information
Type of In-
formation
Comments
5203
>BLOCK Freq.
SP
>BLOCK frequency protection
5206
>BLOCK f1
SP
>BLOCK frequency protection stage f1
5207
>BLOCK f2
SP
>BLOCK frequency protection stage f2
5208
>BLOCK f3
SP
>BLOCK frequency protection stage f3
5209
>BLOCK f4
SP
>BLOCK frequency protection stage f4
5211
Freq. OFF
OUT
Frequency protection is switched OFF
5212
Freq. BLOCKED
OUT
Frequency protection is BLOCKED
5213
Freq. ACTIVE
OUT
Frequency protection is ACTIVE
5215
Freq UnderV Blk
OUT
Frequency protection undervoltage Blk
5232
f1 picked up
OUT
Frequency protection: f1 picked up
5233
f2 picked up
OUT
Frequency protection: f2 picked up
5234
f3 picked up
OUT
Frequency protection: f3 picked up
5235
f4 picked up
OUT
Frequency protection: f4 picked up
5236
f1 TRIP
OUT
Frequency protection: f1 TRIP
5237
f2 TRIP
OUT
Frequency protection: f2 TRIP
5238
f3 TRIP
OUT
Frequency protection: f3 TRIP
5239
f4 TRIP
OUT
Frequency protection: f4 TRIP
5240
Time Out f1
OUT
Frequency protection: TimeOut Stage f1
5241
Time Out f2
OUT
Frequency protection: TimeOut Stage f2
5242
Time Out f3
OUT
Frequency protection: TimeOut Stage f3
5243
Time Out f4
OUT
Frequency protection: TimeOut Stage f4
Addr.
Parameter
Setting Options
Default Setting
Comments