Appendix
A.6 Functional Scope
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
682
A.6
Functional Scope
Addr.
Parameter
Setting Options
Default Setting
Comments
103
Grp Chge OPTION
Disabled
Enabled
Disabled
Setting Group Change Option
110
Trip mode
3pole only
1-/3pole
3pole only
Trip mode
112
DIFF.PROTECTION
Enabled
Disabled
Enabled
Differential protection
115
Phase Distance
Quadrilateral
MHO
Disabled
Quadrilateral
Phase Distance
116
Earth Distance
Quadrilateral
MHO
Disabled
Quadrilateral
Earth Distance
117
Dis. PICKUP
Z< (quadrilat.)
I> (overcurr.)
U/I
U/I/
ϕ
Disabled
Z< (quadrilat.)
Distance protection pickup
program
119
Iph>(Z1)
Disabled
Enabled
Disabled
Additional Threshold Iph>(Z1)
120
Power Swing
Disabled
Enabled
Disabled
Power Swing detection
121
Teleprot. Dist.
PUTT (Z1B)
PUTT (Pickup)
POTT
Dir.Comp.Pickup
UNBLOCKING
BLOCKING
Rev. Interlock
Pilot wire comp
Disabled
Disabled
Teleprotection for Distance prot.
122
DTT Direct Trip
Disabled
Enabled
Disabled
DTT Direct Transfer Trip
124
HS/SOTF-O/C
Disabled
Enabled
Disabled
Instantaneous HighSpeed/SOTF
Overcurrent
125
Weak Infeed
Disabled
Enabled
Logic no. 2
Disabled
Weak Infeed (Trip and/or Echo)
126
Back-Up O/C
Disabled
TOC IEC
TOC ANSI
TOC IEC
Backup overcurrent
130
Sens. Earth Flt
Disabled
Enabled
Disabled
Sensitive Earth Flt.(comp/ isol.
starp.)
131
Earth Fault O/C
Disabled
TOC IEC
TOC ANSI
TOC Logarithm.
Definite Time
U0 inverse
Sr inverse
Disabled
Earth fault overcurrent