Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
688
1235
I-DIF>>SWITCHON
Diff. Prot
1A
0.8 .. 100.0 A;
∞
1.2 A
I-DIFF>>: Value under switch on
cond.
5A
4.0 .. 500.0 A;
∞
6.0 A
1301
I-TRIP SEND
Intertrip
YES
NO
NO
State of transmit. the intertrip
command
1302
I-TRIP RECEIVE
Intertrip
Alarm only
Trip
Trip
Reaction if intertrip command is
receiv.
1303
T-ITRIP BI
Intertrip
0.00 .. 30.00 sec
0.02 sec
Delay for intertrip via binary input
1304
T-ITRIP PROL BI
Intertrip
0.00 .. 30.00 sec
0.00 sec
Prolongation for intertrip via
bin.input
1401
HSD
HighSpeedDIS
ON
OFF
OFF
High Speed Distance Protection
1402
HSD ZHSD
HighSpeedDIS
1A
0.050 .. 600.000
Ω
2.000
Ω
High Speed Distance ZHSD
5A
0.010 .. 120.000
Ω
0.400
Ω
1407
BL.ZHSD.DIFF.A
HighSpeedDIS
YES
NO
NO
High Speed Distance blocked if
Diff.A
1501
FCT Distance
Dis. General
ON
OFF
ON
Distance protection
1502
Minimum Iph>
Dis. General
1A
0.05 .. 4.00 A
0.10 A
Phase Current threshold for dist.
meas.
5A
0.25 .. 20.00 A
0.50 A
1503
3I0> Threshold
Dis. General
1A
0.05 .. 4.00 A
0.10 A
3I0 threshold for neutral current
pickup
5A
0.25 .. 20.00 A
0.50 A
1504
3U0> Threshold
Dis. General
1 .. 100 V;
∞
5 V
3U0 threshold zero seq. voltage
pickup
1505
3U0> COMP/ISOL.
Dis. General
10 .. 200 V;
∞
∞
V
3U0> pickup (comp/ isol. star-
point)
1507A
3I0>/ Iphmax
Dis. General
0.05 .. 0.30
0.10
3I0>-pickup-stabilisation (3I0>
/Iphmax)
1508
SER-COMP.
Dis. General
NO
YES
NO
Series compensated line
1509A
E/F recognition
Dis. General
3I0> OR 3U0>
3I0> AND 3U0>
3I0> OR 3U0>
criterion of earth fault recognition
1510
Start Timers
Dis. General
on Dis. Pickup
on Zone Pickup
on Dis. Pickup
Condition for zone timer start
1511
Distance Angle
P.System Data 2
Dis. General
30 .. 90 °
85 °
Angle of inclination, distance
charact.
1515
Paral.Line Comp
Dis. General
NO
YES
YES
Mutual coupling parall.line com-
pensation
1520
PHASE PREF.2phe
Dis. General
L3 (L1) ACYCLIC
L1 (L3) ACYCLIC
L2 (L1) ACYCLIC
L1 (L2) ACYCLIC
L3 (L2) ACYCLIC
L2 (L3) ACYCLIC
L3 (L1) CYCLIC
L1 (L3) CYCLIC
All loops
L3 (L1) ACYCLIC
Phase preference for 2ph-e faults
1521A
2Ph-E faults
Dis. General
Block leading Ø
Block lagging Ø
All loops
Ø-Ø loops only
Ø-E loops only
Block leading Ø
Loop selection with 2Ph-E faults
1523
Uph-ph unbal.
Dis. General
5 .. 50 %
25 %
Max Uph-ph unbal. for 1ph Flt.
detection
1532
SOTF zone
Dis. General
PICKUP
Zone Z1B
Z1B undirect.
Zone Z1
Z1 undirect.
Inactive
Inactive
Instantaneous trip after Switch-
OnToFault
1533
Z1 blkd by diff
Dis. General
YES
NO
YES
Zone Z1 blocked by diff. active
1541
R load (Ø-E)
Dis. General
1A
0.100 .. 600.000
Ω
;
∞
∞ Ω
R load, minimum Load Imped-
ance (ph-e)
5A
0.020 .. 120.000
Ω
;
∞
∞ Ω
1541
R load
Dis. General
1A
0.100 .. 600.000
Ω
;
∞
∞ Ω
R load, minimum Load Imped-
ance
5A
0.020 .. 120.000
Ω
;
∞
∞ Ω
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments