Appendix
A.8 Information List
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
718
1402
>BF: Switch off breaker fail pro-
tection (>BF off)
Breaker Failure
SP
*
*
*
LED BI
BO
1403
>BLOCK Breaker failure
(>BLOCK BkrFail)
Breaker Failure
SP
on
off
*
*
LED BI
BO
166
103
1
Yes
1404
>BF Activate 3I0> threshold
(>BFactivate3I0>)
Breaker Failure
SP
on
off
*
*
LED BI
BO
1415
>BF: External start 3pole (>BF
Start 3pole)
Breaker Failure
SP
on
off
*
*
LED BI
BO
1424
>BF: Start only delay time T2
(>BF STARTonlyT2)
Breaker Failure
SP
on
off
on off
*
LED BI
BO
1432
>BF: External release (>BF re-
lease)
Breaker Failure
SP
on
off
*
*
LED BI
BO
1435
>BF: External start L1 (>BF Start
L1)
Breaker Failure
SP
on
off
*
*
LED BI
BO
1436
>BF: External start L2 (>BF Start
L2)
Breaker Failure
SP
on
off
*
*
LED BI
BO
1437
>BF: External start L3 (>BF Start
L3)
Breaker Failure
SP
on
off
*
*
LED BI
BO
1439
>BF: External start 3pole (w/o
current) (>BF Start w/o I)
Breaker Failure
SP
on
off
*
*
LED BI
BO
1440
Breaker failure prot. ON/OFF via
BI (BkrFailON/offBI)
Breaker Failure
IntSP
on
off
*
*
LED
BO
1451
Breaker failure is switched OFF
(BkrFail OFF)
Breaker Failure
OUT
on
off
*
*
LED
BO
166
151
1
Yes
1452
Breaker failure is BLOCKED
(BkrFail BLOCK)
Breaker Failure
OUT
on
off
on off
*
LED
BO
166
152
1
Yes
1453
Breaker failure is ACTIVE (Bkr-
Fail ACTIVE)
Breaker Failure
OUT
*
*
*
LED
BO
166
153
1
Yes
1461
Breaker failure protection started
(BF Start)
Breaker Failure
OUT
*
on off
*
LED
BO
166
161
2
Yes
1472
BF Trip T1 (local trip) - only
phase L1 (BF T1-TRIP 1pL1)
Breaker Failure
OUT
*
on
*
LED
BO
1473
BF Trip T1 (local trip) - only
phase L2 (BF T1-TRIP 1pL2)
Breaker Failure
OUT
*
on
*
LED
BO
1474
BF Trip T1 (local trip) - only
phase L3 (BF T1-TRIP 1pL3)
Breaker Failure
OUT
*
on
*
LED
BO
1476
BF Trip T1 (local trip) - 3pole (BF
T1-TRIP L123)
Breaker Failure
OUT
*
on
*
LED
BO
1493
BF Trip in case of defective CB
(BF TRIP CBdefec)
Breaker Failure
OUT
*
on
*
LED
BO
1494
BF Trip T2 (busbar trip) (BF T2-
TRIP(bus))
Breaker Failure
OUT
*
on
*
LED
BO
192
85
2
No
1495
BF Trip End fault stage (BF
EndFlt TRIP)
Breaker Failure
OUT
*
on
*
LED
BO
1496
BF Pole discrepancy pickup (BF
CBdiscrSTART)
Breaker Failure
OUT
*
on off
*
LED
BO
1497
BF Pole discrepancy pickup L1
(BF CBdiscr L1)
Breaker Failure
OUT
*
on off
*
LED
BO
1498
BF Pole discrepancy pickup L2
(BF CBdiscr L2)
Breaker Failure
OUT
*
on off
*
LED
BO
1499
BF Pole discrepancy pickup L3
(BF CBdiscr L3)
Breaker Failure
OUT
*
on off
*
LED
BO
1500
BF Pole discrepancy Trip (BF
CBdiscr TRIP)
Breaker Failure
OUT
*
on
*
LED
BO
1503
>BLOCK Thermal Overload Pro-
tection (>BLK ThOverload)
Therm. Overload
SP
*
*
*
LED BI
BO
167
3
1
Yes
No.
Description
Function
Type
of In-
for-
matio
n
Log Buffers
Configurable in Matrix
IEC 60870-5-103
Ev
ent Log
O
N
/O
FF
T
rip (
F
aul
t)
Log On/
O
ff
G
round
Fault Log ON/
O
FF
M
a
rk
e
d
i
n
O
s
ci
ll.
Re
c
o
rd
LED
B
ina
ry
I
n
pu
t
Function
Key
Rela
y
Chatte
r Suppr
e
ssion
Ty
p
e
In
form
ati
on Nu
mbe
r
Dat
a
Un
it
Ge
ne
ra
l Int
e
rro
ga
ti
on