Appendix
A.8 Information List
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
719
1511
Thermal Overload Protection
OFF (Th.Overload OFF)
Therm. Overload
OUT
on
off
*
*
LED
BO
167
11
1
Yes
1512
Thermal Overload Protection
BLOCKED (Th.Overload BLK)
Therm. Overload
OUT
on
off
on off
*
LED
BO
167
12
1
Yes
1513
Thermal Overload Protection
ACTIVE (Th.O/L ACTIVE)
Therm. Overload
OUT
on
off
*
*
LED
BO
167
13
1
Yes
1515
Th. Overload: Current Alarm (I
alarm) (Th.O/L I Alarm)
Therm. Overload
OUT
on
off
*
*
LED
BO
167
15
1
Yes
1516
Th. Overload Alarm: Near
Thermal Trip (Th.O/L
Θ
Alarm)
Therm. Overload
OUT
on
off
*
*
LED
BO
167
16
1
Yes
1517
Th. Overload Pickup before trip
(Th.O/L Pickup)
Therm. Overload
OUT
on
off
*
*
LED
BO
167
17
1
Yes
1521
Th. Overload TRIP command
(Th.O/L TRIP)
Therm. Overload
OUT
*
on
*
LED
BO
167
21
2
Yes
2054
Emergency mode (Emer. mode)
Device
OUT
on
off
on off
*
LED
BO
192
37
1
Yes
2701
>AR: Switch on auto-reclose
function (>AR on)
Auto Reclose
SP
*
*
*
LED BI
BO
40
1
1
Yes
2702
>AR: Switch off auto-reclose
function (>AR off)
Auto Reclose
SP
*
*
*
LED BI
BO
40
2
1
Yes
2703
>AR: Block auto-reclose function
(>AR block)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
3
1
Yes
2711
>External start of internal Auto
reclose (>AR Start)
Auto Reclose
SP
*
on
*
LED BI
BO
40
11
2
Yes
2712
>AR: External trip L1 for AR start
(>Trip L1 AR)
Auto Reclose
SP
*
on
*
LED BI
BO
40
12
2
Yes
2713
>AR: External trip L2 for AR start
(>Trip L2 AR)
Auto Reclose
SP
*
on
*
LED BI
BO
40
13
2
Yes
2714
>AR: External trip L3 for AR start
(>Trip L3 AR)
Auto Reclose
SP
*
on
*
LED BI
BO
40
14
2
Yes
2715
>AR: External 1pole trip for AR
start (>Trip 1pole AR)
Auto Reclose
SP
*
on
*
LED BI
BO
40
15
2
Yes
2716
>AR: External 3pole trip for AR
start (>Trip 3pole AR)
Auto Reclose
SP
*
on
*
LED BI
BO
40
16
2
Yes
2727
>AR: Remote Close signal (>AR
RemoteClose)
Auto Reclose
SP
*
on
*
LED BI
BO
40
22
2
Yes
2731
>AR: Sync. release from ext.
sync.-check (>Sync.release)
Auto Reclose
SP
*
*
*
LED BI
BO
40
31
2
Yes
2737
>AR: Block 1pole AR-cycle
(>BLOCK 1pole AR)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
32
1
Yes
2738
>AR: Block 3pole AR-cycle
(>BLOCK 3pole AR)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
33
1
Yes
2739
>AR: Block 1phase-fault AR-
cycle (>BLK 1phase AR)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
34
1
Yes
2740
>AR: Block 2phase-fault AR-
cycle (>BLK 2phase AR)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
35
1
Yes
2741
>AR: Block 3phase-fault AR-
cycle (>BLK 3phase AR)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
36
1
Yes
2742
>AR: Block 1st AR-cycle (>BLK
1.AR-cycle)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
37
1
Yes
2743
>AR: Block 2nd AR-cycle (>BLK
2.AR-cycle)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
38
1
Yes
2744
>AR: Block 3rd AR-cycle (>BLK
3.AR-cycle)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
39
1
Yes
2745
>AR: Block 4th and higher AR-
cycles (>BLK 4.-n. AR)
Auto Reclose
SP
on
off
*
*
LED BI
BO
40
40
1
Yes
No.
Description
Function
Type
of In-
for-
matio
n
Log Buffers
Configurable in Matrix
IEC 60870-5-103
Ev
ent Log
O
N
/O
FF
T
rip (
F
aul
t)
Log On/
O
ff
G
round
Fault Log ON/
O
FF
M
a
rk
e
d
i
n
O
s
ci
ll.
Re
c
o
rd
LED
B
ina
ry
I
n
pu
t
Function
Key
Rela
y
Chatte
r Suppr
e
ssion
Ty
p
e
In
form
ati
on Nu
mbe
r
Dat
a
Un
it
Ge
ne
ra
l Int
e
rro
ga
ti
on