Functions
2.2 Protection Data Interfaces and Protection Data Topology
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
88
2.2.3.2
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
Setting Options
Default Setting
Comments
4501
STATE PROT I 1
ON
OFF
ON
State of protection interface 1
4502
CONNEC. 1 OVER
F.optic direct
Com conv 64 kBit/s
Com conv 128 kBit/s
Com conv 512 kBit/s
C37.94 1 slot
C37.94 2 slots
C37.94 4 slots
C37.94 8 slots
F.optic direct
Connection 1 over
4505A
PROT 1 T-DELAY
0.1 .. 30.0 ms
30.0 ms
Prot 1: Maximal permissible delay
time
4506A
PROT 1 UNSYM.
0.000 .. 3.000 ms
0.100 ms
Prot 1: Diff. in send and receive
time
4509
T-DATA DISTURB
0.05 .. 2.00 sec
0.10 sec
Time delay for data disturbance
alarm
4510
T-DATAFAIL
0.0 .. 60.0 sec
6.0 sec
Time del for transmission failure
alarm
4511
PI1 SYNCMODE
TEL and GPS
TEL or GPS
GPS SYNC OFF
TEL and GPS
PI1 Synchronizationmode
4512
Td ResetRemote
0.00 .. 300.00 sec;
∞
0.00 sec
Remote signal RESET DELAY for
comm.fail
4513A
PROT1 max ERROR
0.5 .. 20.0 %
1.0 %
Prot 1: Maximal permissible error
rate
4515A
PI1 BLOCK UNSYM
YES
NO
YES
Prot.1: Block. due to unsym. delay
time
4601
STATE PROT I 2
ON
OFF
ON
State of protection interface 2
4602
CONNEC. 2 OVER
F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
C37.94 1 slot
C37.94 2 slots
C37.94 4 slots
C37.94 8 slots
F.optic direct
Connection 2 over
4605A
PROT 2 T-DELAY
0.1 .. 30.0 ms
30.0 ms
Prot 2: Maximal permissible delay
time
4606A
PROT 2 UNSYM.
0.000 .. 3.000 ms
0.100 ms
Prot 2: Diff. in send and receive
time
4611
PI2 SYNCMODE
TEL and GPS
TEL or GPS
GPS SYNC OFF
TEL and GPS
PI2 Synchronizationmode
4613A
PROT2 max ERROR
0.5 .. 20.0 %
1.0 %
Prot 2: Maximal permissible error
rate