Functions
2.17 Automatic Reclosure Function (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
343
2.17.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
Setting Options
Default Setting
Comments
3401
AUTO RECLOSE
OFF
ON
ON
Auto-Reclose Function
3402
CB? 1.TRIP
YES
NO
NO
CB ready interrogation at 1st trip
3403
T-RECLAIM
0.50 .. 300.00 sec
3.00 sec
Reclaim time after successful AR
cycle
3403
T-RECLAIM
0.50 .. 300.00 sec; 0
3.00 sec
Reclaim time after successful AR
cycle
3404
T-BLOCK MC
0.50 .. 300.00 sec; 0
1.00 sec
AR blocking duration after manual
close
3406
EV. FLT. RECOG.
with PICKUP
with TRIP
with TRIP
Evolving fault recognition
3407
EV. FLT. MODE
Stops AutoRecl
starts 3p AR
starts 3p AR
Evolving fault (during the dead
time)
3408
T-Start MONITOR
0.01 .. 300.00 sec
0.50 sec
AR start-signal monitoring time
3409
CB TIME OUT
0.01 .. 300.00 sec
3.00 sec
Circuit Breaker (CB) Supervision
Time
3410
T RemoteClose
0.00 .. 300.00 sec;
∞
0.20 sec
Send delay for remote close
command
3411A
T-DEAD EXT.
0.50 .. 300.00 sec;
∞
∞
sec
Maximum dead time extension
3420
AR WITH DIFF
YES
NO
YES
AR with differential protection ?
3421
AR w/ SOTF-O/C
YES
NO
YES
AR with switch-onto-fault overcur-
rent ?
3422
AR w/ DIST.
YES
NO
YES
AR with distance protection ?
3423
AR WITH I.TRIP
YES
NO
YES
AR with intertrip ?
3424
AR w/ DTT
YES
NO
YES
AR with direct transfer trip ?
3425
AR w/ BackUpO/C
YES
NO
YES
AR with back-up overcurrent ?
3426
AR w/ W/I
YES
NO
YES
AR with weak infeed tripping ?
3427
AR w/ EF-O/C
YES
NO
YES
AR with earth fault overcurrent
prot. ?
3430
AR TRIP 3pole
YES
NO
YES
3pole TRIP by AR
3431
DLC / RDT
WITHOUT
DLC
WITHOUT
Dead Line Check / Reduced Dead
Time
3433
T-ACTION ADT
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3434
T-MAX ADT
0.50 .. 3000.00 sec
5.00 sec
Maximum dead time