Functions
2.18 Synchronism and Voltage Check (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
358
Note
The closing functions of the device issue individual output indications for the corresponding close command.
Be sure that the output indications are assigned to the correct output relays.
No. 2851
„AR CLOSE Cmd.“
for CLOSE via command of the automatic reclosure,
No. 562
„Man.Close Cmd“
for manual CLOSE via binary input,
No. 2961
„Sync.CloseCmd“
for CLOSE via synchronism check (not required if synchronism check releases
the other CLOSE commands),
No. 7329
„CB1-TEST close“
for CLOSE by circuit breaker test,
additionally CLOSE command via control, e.g.
„Brk Close“
.
No. 510
„Relay CLOSE“
general CLOSE command. It comprises all CLOSE commands described above.
Notes on the Information List
The most important information messages of the device are briefly explained below, except those already de-
tailed in the following lists or in the previous paragraphs.
„>Sync. Start MC“
(No. 2905)
Binary input which enables direct initiation of the synchronism check with setting parameters for manual close.
This initiation with setting parameter for manual close has always precedence if binary inputs
„>Sync. Start
MC“
(No. 2905) and
„>Sync. Start AR“
(No. 2906, see below) are activated at the same time.
„>Sync. Start AR“
(No 2906)
Measuring request from an external automatic reclosure device. The parameters of synchronism check set for
automatic reclosure are valid here.
„Sync. req.CNTRL“
(No 2936)
Measurement request of the control function; this request is evaluated on event-triggered basis and only gen-
erated if the control issues a measurement request.
„Sync. release“
(No 2951)
Release signal to an external automatic reclosure device.
2.18.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
Setting Options
Default Setting
Comments
3501
FCT Synchronism
ON
OFF
ON:w/o CloseCmd
ON
Synchronism and Voltage Check
function
3502
Dead Volt. Thr.
1 .. 100 V
5 V
Voltage threshold dead line / bus