Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
531
3.3
Commissioning
WARNING!
Warning of dangerous voltages when operating an electrical device
Non-observance of the following measures can result in death, personal injury or substantial property damage.
Only qualified people shall work on and around this device. They must be thoroughly familiar with all warnings
and safety notices in this instruction manual as well as with the applicable safety steps, safety regulations, and
precautionary measures.
Before making any connections, the device must be earthed at the protective conductor terminal.
Hazardous voltages can exist in the power supply and at the connections to current transformers, voltage trans-
formers, and test circuits.
Hazardous voltages can be present in the device even after the power supply voltage has been removed (ca-
pacitors can still be charged).
After removing voltage from the power supply, wait a minimum of 10 seconds before re-energizing the power
supply. This wait allows the initial conditions to be firmly established before the device is re-energized.
The limit values given in Technical Data must not be exceeded, neither during testing nor during commission-
ing.
For tests with a secondary test equipment ensure that no other measurement voltages are connected and the
trip and close commands to the circuit breakers are blocked, unless otherwise specified.
DANGER!
Hazardous voltages during interruptions in secondary circuits of current transformers
Non-observance of the following measure will result in death, severe personal injury or substantial property
damage.
Short-circuit the current transformer secondary circuits before current connections to the device are opened.
During the commissioning procedure, switching operations must be carried out. The tests described require
that they can be done without danger. They are accordingly not meant for operational checks.
WARNING!
Warning of dangers evolving from improper primary tests
Non-observance of the following measure can result in death, personal injury or substantial property damage.
Primary tests may only be carried out by qualified persons who are familiar with commissioning protection sys-
tems, with managing power systems and the relevant safety rules and guidelines (switching, earthing etc.).