Technical Data
4.12 Weak Infeed Tripping (French Specification/optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
610
4.12
Weak Infeed Tripping (French Specification/optional)
Operating Mode
Undervoltage
Times
Phase segregated undervoltage detection after reception of a carrier signal from the remote end
Setting value U
PhE
<
0.10 to 1.00
Increments 0.01
Dropout/pickup ratio
Approx. 1.1
Pickup tolerance
≤
5 %
Receive prolongation
0.00 s to 30.00 s
Increments 0.01 s
Extension time 3
I
0>
0.00 s to 30.00 s
Increments 0.01 s
Alarm time 3
I
0>
0.00 s to 30.00 s
Increments 0.01 s
Delay (single-pole)
0.00 s to 30.00 s
Increments 0.01 s
Delay (multi-pole)
0.00 s to 30.00 s
Increments 0.01 s
Time constant
τ
1 s to 60 s
Increments 1 s
Pickup tolerance
1 % of setting value or 10 ms