Appendix
A.5 Protocol-dependent Functions
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
681
A.5
Protocol-dependent Functions
Protocol
→
IEC 60870-5-103
IEC 61850
Ethernet (EN100)
PROFIBUS FMS Profibus DP
DNP 3.0
Function
↓
Operational Mea-
sured Values
Yes
Yes
Yes
Yes
Yes
Metered Values
Yes
Yes
Yes
Yes
Yes
Fault Recording
Yes
Yes
Yes
No, only via addi-
tional service in-
terface
No, only via additional
service interface
Remote Relay
Setting
No, only via addi-
tional service inter-
face
Yes, with DIGSI via
Ethernet
Yes, with DIGSI
via PROFIBUS
No, only via addi-
tional service in-
terface
No, only via additional
service interface
User-defined
Alarms and Switch-
ing Objects
Yes
Yes
Yes
Predefined
„User-defined
Alarms“ in CFC
Predefined „User-
defined Alarms“ in
CFC
Time Synchroniza-
tion
Via protocol;
DCF77/IRIG-B/
GPS;
Interface;
Protection Data In-
terface;
Binary input
Via protocol
(NPT);
DCF77/IRIG-B;
Interface;
Protection Data In-
terface;
Binary input
Via protocol;
DCF77/IRIG-B/
GPS;
Interface;
Protection Data
Interface;
Binary Input
Via DCF77/IRIG-
B/GPS;
Interface;
Protection Data
Interface;
Binary Input
Via protocol;
DCF77/IRIG-B/GPS;
Interface;
Protection Data Inter-
face;
Binary Input
Messages with
time stamp
Yes
Yes
Yes
YES
Yes
Commissioning tools
Alarm and Mea-
sured Value Trans-
mission Blocking
Yes
Yes
Yes
No
No
Generate
test alarms
Yes
Yes
Yes
No
No
Physical Mode
Asynchronous
Synchronous
Asynchronous
Asynchronous
Asynchronous
Transmission Mode Cyclic/Event
Cyclical/Event
Cyclic/Event
Cyclic
Cyclic/Event
Baud Rate
4800 to 38400
up to 100 MBaud
up to 1.5 Mbaud up to 1.5 Mbaud 2400 to 19200
Type
RS232/RS485
Fibre-optic cables
Ethernet TP
Optical or electrical
RS485
Fibre-optic
cables
Double ring
RS485
Fibre-optic
cables
Double ring
RS485
Fibre-optic cables