Standard mapping 3-1
2-5
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
2.2.4
Registers 10020 to 10023: Inverse time overcurrent protection
2.2.5
Registers 10024 to 10026: Thermal overload protection
2.2.6
Registers 10027 to 10031: Unbalanced load protection
2.2.7
Registers 10032 to 10036: Sensitive ground fault protection
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10020
51V Ph A PU
1 = 51V Phase A picked up
1896
10021
51V Ph B PU
1 = 51V Phase B picked up
1897
10022
51V Ph C PU
1 = 51V Phase C picked up
1898
10023
51V TRIP
1 = 51V TRIP
1900
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10024
49 O/L I Alarm
1 = 49 Overload Current Alarm (I alarm)
1515
10025
49 O/L
Θ
Alarm
1 = 49 Thermal Overload Alarm
1516
10026
49 Th O/L TRIP
1 = 49 Thermal Overload TRIP
1521
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10027
46-1 Warn
1 = 46-1 Current warning stage
5156
10028
46-1 picked up
1 = 46-1 picked up
5165
10029
46-2 picked up
1 = 46-2 picked up
5159
10030
46-2 TRIP
1 = 46-2 TRIP of current stage
5160
10031
46-
Θ
TRIP
1 = 46 TRIP of thermal stage
5161
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10032
Failure 64R In<
1 = Failure 64R In<: measuring circuit
5396
10033
50Ns-1 Pickup
1 = 50Ns-1 Pickup
1224
10034
50Ns-1 TRIP
1= 50Ns-1 TRIP
1226
10035
50Ns-2 Pickup
1 = 50Ns-2 Pickup
1221
10036
50Ns-2 TRIP
1 = 50Ns-2 TRIP
1223
Summary of Contents for SIPROTEC4 7UM62
Page 6: ...Preface iv SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 8: ...Revision index vi SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 12: ...Table of contents x SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 58: ...Standard mapping 3 2 3 20 SIPROTEC Modbus Bus mapping 7UM62 C53000 L1840 C009 03 ...
Page 60: ...Glossary 4 2 SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...