Standard mapping 3-2
3-8
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
3.2.16 Register 10071: Fuse Failure Monitor
3.2.17 Registers 10072 to 10077: Underexcitation protection
3.2.18 Registers 10078 to 10079: Circuit breaker failure protection
3.2.19 Registers 10080 to 10087: Impedance protection
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10071
VT Fuse Failure
1 = Voltage Transformer Fuse Failure
6575
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10072
40 Vexc failure
1 = 40 Exc. voltage failure recognized
5336
10073
40 picked up
1 = 40 picked up
5337
10074
40-1 TRIP
1 = 40 characteristic 1 TRIP
5344
10075
40-2 TRIP
1 = 40 characteristic 2 TRIP
5345
10076
40&V<TRIP
1 = 40 characteristic&Vexc< TRIP
5346
10077
40-3 TRIP
1 = 40 characteristic 3 TRIP
5343
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10078
50BF pickup
1 = 50BF picked up
1455
10079
50BF TRIP
1 = 50BF TRIP
1471
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10080
21 Fault Ph A
1 = 21 Fault detection , Phase A
3967
10081
21 Fault Ph B
1 = 21 Fault detection , Phase B
3968
10082
21 Fault Ph C
1 = 21 Fault detection , Phase C
3969
10083
21 I> & U<
1 = 21 O/C with undervoltage seal in
3970
10084
21 Z1< TRIP
1 = 21 Z1< TRIP
3977
10085
21 Z1B< TRIP
1 = 21 Z1B< TRIP
3978
10086
21 Z2< TRIP
1 = 21 Z2< TRIP
3979
10087
21 T3> TRIP
1 = 21 T3> TRIP
3980
Summary of Contents for SIPROTEC4 7UM62
Page 6: ...Preface iv SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 8: ...Revision index vi SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 12: ...Table of contents x SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 58: ...Standard mapping 3 2 3 20 SIPROTEC Modbus Bus mapping 7UM62 C53000 L1840 C009 03 ...
Page 60: ...Glossary 4 2 SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...