Standard mapping 3-1
2-7
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
2.2.12 Registers 10051 to 10058: Frequency protection
2.2.13 Registers 10059 to 10063: Overexcitation protection
2.2.14 Registers 10064 to 10066: Reverse power protection
2.2.15 Registers 10067 to 10070: Forward power supervision
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10051
81-1 picked up
1 = 81-1 picked up
5232
10052
81-2 picked up
1 = 81-2 picked up
5233
10053
81-3 picked up
1 = 81-3 picked up
5234
10054
81-4 picked up
1 = 81-4 picked up
5235
10055
81-1 TRIP
1 = 81-1 TRIP
5236
10056
81-2 TRIP
1 = 81-2 TRIP
5237
10057
81-3 TRIP
1 = 81-3 TRIP
5238
10058
81-4 TRIP
1 = 81-4 TRIP
5239
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10059
24 warn
1 = 24 V/f warning stage
5367
10060
24-1 picked up
1 = 24-1 V/f> picked up
5370
10061
24-2 picked up
1 = 24-2 V/f>> picked up
5373
10062
24 th.TRIP
1 = 24 TRIP of thermal stage
5372
10063
24-2 TRIP
1 = 24-2 TRIP of V/f>> stage
5371
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10064
32R picked up
1 = 32R picked up
5096
10065
32R TRIP
1 = 32R TRIP
5097
10066
32R+SV TRIP
1 = 32R TRIP with stop valve
5098
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10067
32F< picked up
1 = 32F P< stage picked up
5126
10068
32F> picked up
1 = 32F P> stage picked up
5127
10069
32F P< TRIP
1 = 32F P< stage TRIP
5128
10070
32F P> TRIP
1 = 32F P> stage TRIP
5129
Summary of Contents for SIPROTEC4 7UM62
Page 6: ...Preface iv SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 8: ...Revision index vi SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 12: ...Table of contents x SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Page 58: ...Standard mapping 3 2 3 20 SIPROTEC Modbus Bus mapping 7UM62 C53000 L1840 C009 03 ...
Page 60: ...Glossary 4 2 SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...