Operation
9.3 RESET after release
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
Manual, 09/2014, A5E03656507420A/RS-AA/002
79
Setting the RESET function on the 3RB30/3RB31 solid-state overload relay
In the case of the 3RB30/3RB31 solid-state overload relays, a slide switch can be used to
choose between automatic and manual reset.
As an alternative to the local reset options, an electrical remote RESET (manual / automatic)
can be implemented on 3RB31 solid-state overload relays by applying a 24 V DC voltage at
terminals A3 and A4, which actuates an internal relay. To ensure that the internal relay will
reliably switch, the voltage needs to be applied for at least 200 ms. During switching, the
relay's current consumption amounts to as much as 200 mA for up to 20 ms, after which it
drops to below 10 mA.
Table 9- 2
Switching between manual and automatic on 3RB30/3RB31 solid-state overload relays
Step
Instructions
Figure
1
Using a screwdriver, slide the switch to the
required position.
Reference
More information ...
Can be found in the Chapter ...
about optional mechanical and electrical RESET
modules