Functions
7.12 3RW5 HMI High Feature
SIRIUS 3RW50 soft starter
150
Manual, 09/2019, A5E35628455002A/RS-AA/001
Process image input (PII)
Process data
Process image
DI 0.0
Ready (automatic)
DI 0.1
Motor On
DI 0.2
Group error
DI 0.3
Group warning
DI 0.4
Input 1
DI 1.0
Motor current Iact-bit0
DI 1.1
Motor current Iact-bit1
DI 1.2
Motor current Iact-bit2
DI 1.3
Motor current Iact-bit3
DI 1.4
Motor current Iact-bit4
DI 1.5
Motor current Iact-bit5
DI 1.6
Manual operation local
DI 1.7
Ramp operation
DI 2.0
Motor CW
DI 2.4
Starting mode active
DI 2.5
Operation / bypass active
DI 2.6
Stop mode active
DI 2.7
Test operation active
DI 3.0
Thermal motor model overload
DI 3.1
Temperature sensor overload
DI 3.2
Switching element overload
DI 3.3
Cooling time active
DI 3.4
Device error
AI 4 (Float32)
Measured value 1 (factory setting: Phase current I L1 (rms))
AI 8 (Float32)
Measured value 2 (factory setting: Phase current I L2 (rms))
AI 12 (Float32)
Measured value 3 (factory setting: Phase current I L3 (rms))
Process image output (PIQ)
Process data
Process image
DQ 0.0
Motor CW
DQ 0.3
Reset
DQ 0.5
Self-test (user-test)
DQ 3.0
Manual operation local - input controlled
Further information
You will find further information on transferring the process images via a fieldbus in the