Parameters
Parameters
Description
Output signal type
Via the "Output signal type" parameter, you can define with what type of signal
the analog value will be output (current or voltage).
• Deactivated (factory setting)
• 4 ... 20 mA
• 0 ... 10 V
Measured value
Select the measured value to be transferred from the analog output via the
"Measured value" parameter.
• Deactivated
• Phase current I L1 (%)
• Phase current I L2 (%)
• Phase current I L3 (%)
• Phase current average (%)
• Phase current I L1 (rms)
• Phase current I L2 (rms)
• Phase current I L3 (rms)
• Phase current average (rms)
• Line voltage U L1-L2 (rms)
• Line voltage U L2-L3 (rms)
• Line voltage U L3-L1 (rms)
• Active power
• Power factor L1...3
• Active energy import (total)
• Motor temperature rise
• Switching element heating
You will find further information in chapter "Monitoring the measured values
of the 3RW55 soft starter with the 3RW5 HMI High Feature (Page 227)".
Range start value
With parameters "Range start value" and "Range end value", you can define
which value of the analog value to be output corresponds to the lower output
signal value and which to the upper output signal value. The corresponding
value depends on the coding of the measured value to be transferred (Un‐
signed 32).
• Setting of the analog range, e.g. 4 mA = 100
• Setting of the analog range, e.g. 20 mA = 400
Range end value
Functions
8.13 Outputs
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
203