Control commands
Control command
Description
Select parameter set
Parameter set 1
(factory setting)
Select one of the 3 parameter sets.
One parameter set is deactivated when another parameter set is
activated. One parameter set must be active at all times.
Parameter set 2
Parameter set 3
Local/Remote
Changes the location of control.
Control motor
Motor CW
Motor rotates clockwise
Motor CCW
Motor rotates counter-clockwise.
The control command can also be executed in reversing mode (with
ext. contactor).
Stop motor
The activation command to the motor is canceled
Creep speed
1)
Make sure that the control command "Motor CW" or "Motor CCW" is
applied with the control command "Creep speed".
• Activate
• Deactivate (factory setting)
You will find more information in chapter Creep speed (Page 172).
Alternative stopping mode Activate alternative stopping in order to set up an additional stop in
parameter set 1.
• Activate
• Deactivate
You will find more information in chapter Alternative stopping
(Page 163).
Pump cleaning start
This control command is only visible if the pump cleaning function
has been parameterized.
You will find more information in chapter Pump cleaning function
(Page 182).
Reset
Execute a RESET.
You will find more information in chapter Reset (Page 173).
Disable Quick-stop
Motor does not stop despite pending ON command of Quick-stop.
You will find more information in chapter Quick-stop (Page 174).
Emergency mode
Emergency start
The system can continue to be operated in the case of system faults
with the "emergency start" function.
• Enable
• Disable
You will find more information in chapter Emergency start
(Page 189).
Emergency run
1), 2)
With the "Emergency run" function, the 3RW55 soft starter can
continue to run with restricted functionality after failure of a power
semiconductor.
• Enable
• Disable
You will find more information in chapter Emergency run
(Page 191).
Functions
8.21 Control via 3RW5 HMI High Feature
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006