Error
Cause
Remedy
Error process image
The process image output (PIQ) con‐
tains invalid control bit combinations
(e.g. control bits for clockwise and
counter-clockwise rotation are set at
the same time).
Check and correct the process image output
(PIQ).
Invalid parameter value
The module is not or is incorrectly
parameterized or parameterization
changes are denied in current oper‐
ating mode.
• Correct and execute parameterization.
• Switch the operating mode and repeat pa‐
rameterization.
No external start parameters received Necessary startup data for the device
are missing.
Check parameterization or startup data re‐
cords.
Self-test error
Unrecoverable error detected after
internal diagnostics (self-test, contac‐
tor contacts, switching element,
etc.).
Switch off the power supply (control supply
voltage) for at least 5 seconds and switch it on
again. If the fault is still present proceed as fol‐
lows:
• Please contact Technical Support (Support
• Replace the device.
Preset unequal actual configuration
Real and configured slot of module is
different.
• Ensure consistency between plugged and
configured module. Possibly the referenced
module has a wiring error.
• After the cause is eliminated, the error self-
acknowledges.
Motor connection wrong
The motor connection type was not
recognized or is different from config‐
uration.
Ensure correct connection.
Missing load
No current flow is detected after the
motor feeder is switched on. Possible
causes:
• Main circuit interrupted (fuse, cir‐
cuit breaker)
• Motor contactor or contactor con‐
trol is defective
• No load
Acknowledgment once the cause has been rec‐
tified.
Loss of phase L1
The main power monitoring detects a
phase failure.
Acknowledgment once the cause has been rec‐
tified.
Loss of phase L2
Loss of phase L3
Overvoltage
The supply voltage is above the toler‐
ance limit.
Change the power supply.
Bypass defective
• Bypass defective
• The error can also be generated
by successive, brief interruptions
of the control supply voltage.
Switch off the power supply (control supply
voltage) for at least 5 seconds and switch it on
again. If the fault is still present proceed as fol‐
lows:
• Please contact Technical Support (Support
• Check bypasses for L1, L2 and L3 and re‐
place any that are defective.
Messages and diagnostics
9.4 Errors and remedial actions of the 3RW55 and 3RW55 Failsafe soft starters
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
254