Execution options
• 3RW5 HMI High Feature
– Menu: "Control > Reset"
– Configured function selection key F1-F9 (Page 117)
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel"
• With a fieldbus via a 3RW5 communication module (only via a 3RW5 PROFINET or PROFIBUS
communication module):
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– With the "Reset" command in data record 93
8.7
Quick-stop
Operating principle
You can assign the "Quick-stop" input action to the digital inputs (Page 194). With a Quick-stop
the motor is shut off in normal operation with the currently set stopping function. Quick-stop is
executed regardless of where master control lies and a group error is not signaled.
You can use the "Disable Quick-stop" (Page 232) command to deactivate execution of the "Quick-
stop" input action.
8.8
Condition Monitoring
8.8.1
Condition Monitoring for plant monitoring
Operating principle
Condition monitoring monitors your plant and is able to detect incipient wear at an early stage.
This enables you to avoid unplanned plant downtimes and loss of production. To do this, you can
specify the response to limit violations of the following functions:
• Current monitoring (Page 175)
• Active power monitoring (Page 177)
• Switching frequency monitoring (Page 178)
• Starting time monitoring (Page 181)
• Pump cleaning function (Page 182)
Functions
8.8 Condition Monitoring
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
174
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006