Process data
Process image
DQ 1.7
Disable Quick-stop
DQ 2.0
Output 3
3), 4)
DQ 2.3
Start pump cleaning
DQ 3.0
Manual operation local - Input controlled
DQ 3.1
Use alternative stopping mode
DQ 3.2
Motor standstill
3)
1)
In order to perform the reset reliably, the control command "Reset" must be present for at least 20 ms.
2)
Control data is relevant for Ex applications.
3)
This function is not available for the 3RW55 Failsafe soft starter.
4)
You can assign the control data "Output 1", "Output 2" and "Output 3" to the digital outputs 1, 2 and 4
of the 3RW55 soft starter in any order via the digital output actions.
5)
You can assign the control data "Output 1" and "Output 2" to the digital outputs 1 and 2 of the 3RW55
Failsafe soft starter in any order via the digital output actions.
6)
Explanation in the following table.
Additional information
The following table describes the assignment of the process images "Parameter set bit 0" and
"Parameter set bit 1":
Assignment of the PIQ bits
Parameter set bit 0
Parameter set bit 1
Process image error
1
1
Parameter set 1 (PS1)
0
0
Parameter set 2 (PS2)
1
0
Parameter set 3 (PS3)
0
1
8.13
Outputs
8.13.1
Digital outputs
Operating principle
The 3RW55 and 3RW55 Failsafe soft starters have 4 digital outputs (DQ1 = output 13, 14; DQ2 =
output 23, 24; DQ3 = output 95, 96, 98; DQ4 = output 43, 44 or output 41, 42 (F‑RQ)) (Page 71)
with which external actuators such as a brake contactor or indicator lamp can be activated.
Using the output actions, you can assign an output action to the digital outputs. Digital output 3
is permanently assigned to the output action "Group error". The 3RW55 Failsafe soft starter has a
safety signaling output (output 4, F‑RQ) (Page 73). This output cannot be parameterized. The
remaining outputs of the 3RW55 and 3RW55 Failsafe soft starters can be assigned an output
action independently of one another.
Functions
8.13 Outputs
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
198