Result
You have adjusted the output signal of the analog output.
PLC at analog output
You can connect the analog output of the 3RW55 and 3RW55 Failsafe soft starters to a free
analog input of the PLC. Make sure that the analog input of the PLC is not connected to the supply
voltage (control supply voltage) of the 3RW55 or 3RW55 Failsafe soft starter and is floating.
8.13.3
Cyclic send data
Operating principle
In the process image input (PII) (Page 196), 3 measured values are transferred that you can
parameterize.
Setting options
• 3RW5 HMI High Feature
Menu: "Parameters > Soft Starter > Outputs > Cyclic send data"
Access protection to the 3RW5 HMI High Feature is not active or has been reset.
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Parameters" > Window "Work area" > "Soft Starter > Outputs > Cyclic send data"
• With a fieldbus via a 3RW5 communication module:
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional (only via a 3RW5 PROFINET
or PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– User program
You can find additional information on the parameters that can be set via the fieldbus in the
manual of the respective 3RW5 communication module.
Functions
8.13 Outputs
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
205