14.Set the date and time (Page 218).
Menu: "Parameter > Soft starter > Date and time"
15.Define the characteristics to be monitored.
– Monitoring the measured values of the 3RW55 soft starter with the 3RW5 HMI High
Feature (Page 227)
Menu: "Monitoring > Measured values"
– Monitoring the process image of the 3RW55 soft starter with the 3RW5 HMI High Feature
(Page 231)
Menu: "Monitoring > Process image"
Note
Last changed parameters
For each parameter set, you can view and directly modify the last 10 changed parameters.
Menu: "Parameters > Soft Starter > Parameter set 1 / 2 / 3 > Last changed parameter"
Result
The 3RW55 or 3RW55 Failsafe soft starter has been parameterized and is ready for
operation. You can now optionally parameterize the 3RW5 HMI High Feature (Page 121).
If you are using a 3RW5 communication module, set its parameters. You will find further
information on operation of the 3RW5 communication module in the manual of the relevant
3RW5 communication module.
6.2
Parameter sets
Operating principle
The 3RW55 and 3RW55 Failsafe soft starters provide 3 individually adjustable parameter sets, of
which only one parameter set is active at a time. Different parameters can be set for each
parameter set. The switchover from one parameter set to another parameter set is only possible
when the motor is switched off. In the factory settings, parameter set 1 is active.
Application
• Starting Dahlander motors (variable-speed drive).
• Starting an application with different load conditions (e.g. empty or full conveyor belt).
• Separate starting of up to 3 drives with different run-up behavior (e.g. compressor and
pump).
Ex operation
In Ex operation (Page 207), only parameter set 1 is active even if another parameter set is
selected. Parameter sets 2 and 3 are not available in this case.
Parameter assignment
6.2 Parameter sets
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
91