User-defined application
To create a user-defined application, perform the following steps:
1. Choose menu item "User defined" and modify the parameters as you require them.
Confirm your input with the OK key.
2. Choose menu item "Reset default parameter".
Confirm your input with the OK key.
3. To save the application parameters, exit the menu with the ESC key and confirm the user
information "Save application parameter?" with the OK key.
The application parameter has been saved. You can reset to the default parameters of the
user-defined application with the menu item "Set default parameter" or with the factory
setting of the 3RW55 or 3RW55 Failsafe soft starter.
Result
The parameterization has been performed for the selected application. You can make changes
to parameters at any time in the "Parameters" menu.
6.4
Suggested settings of the application wizard
Parameter
Small ventilator (fan)
Big ventilator (fan)
Pump
Rated operational current I
e
Rated operational current I
e
of the 3RW55 or 3RW55 Failsafe soft starter used
Starting mode
Voltage ramp + Current limit‐
ing
Torque c Current lim‐
iting
Voltage ramp + Current limit‐
ing
Current limiting value
400%
400%
400%
Starting voltage
40%
Not relevant
40%
Ramp up time
4 s
40 s
10 s
Starting torque
Not relevant
30%
Not relevant
Limiting torque
Not relevant
150%
Not relevant
Stopping mode
Coasting down
Coasting down
Pump stopping mode
Stopping time
Not relevant
Not relevant
10 s
Stopping torque
Not relevant
Not relevant
10%
Trip class
CLASS 10E
CLASS 30E
CLASS 10E
Parameter
Hydraulic pump
Compressors
Conveyor belts
Rated operational current I
e
Rated operational current I
e
of the 3RW55 or 3RW55 Failsafe soft starter used
Starting mode
Voltage ramp + Current limit‐
ing
Torque c Current lim‐
iting
Torque control
Current limiting value
400%
400%
Not relevant
Starting voltage
40%
Not relevant
Not relevant
Ramp up time
10 s
4 s
10 s
Starting torque
Not relevant
50%
70%
Limiting torque
Not relevant
150%
150%
Parameter assignment
6.4 Suggested settings of the application wizard
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
93