Mounting
8.8 Mounting 22.5 mm/17.5 mm devices with device connectors on a standard mounting rail
3SK1 safety relays
Manual, 04/2013, A5E02526190021A/RS-AA/01
133
Step
Instructions
Figure
4
Push the device connectors
together until they engage.
5
Mount the cover on the left of
the first device connector. The
cover is included in the scope
of supply of the device
terminator.
click
click
6
Set the slide switches in the
device termination connector
(Type 1) to the following
positions
•
Below 3SK1 basic unit:
position 2 (bottom; i.e.
open)
•
Below output expansion
3SK1211
position 1 (top; i.e. closed)