Connection
9.1 22.5 mm/17.5 mm devices
3SK1 safety relays
162
Manual, 04/2013, A5E02526190021A/RS-AA/01
9.1.3
Connecting the screw-type terminals
WARNING
Hazardous Voltage
Can Cause Death, Serious Injury, or Property Damage.
Before starting work, therefore, disconnect the system and devices from the power supply.
Requirements
● Cross-tip screwdriver size PZ 1 x 80.
● For suitable connection cross-sections of the cables, see the chapter "Connection data
Procedure
Step Instructions
Figure
1
Insert the relevant cable into square on the
screw-type terminal until it engages.
2
Hold the cable in the screw-type terminal.
3
Tighten the screw with a torque of 0.8 to 1.2 N.
4
Pull on the cable to ensure it is screwed tight.