Display and diagnostics
12.2 Power-up
3SK1 safety relays
Manual, 04/2013, A5E02526190021A/RS-AA/01
189
12.2
Power-up
Display mode during power-up / parameterization in configuration mode
LED
Display
Explanation
Yellow or yellow flashing Monitored start
(1) DEVICE
Off
Autostart
Yellow or yellow flashing Cross-circuit detection ON
(2) OUT
Off
Cross-circuit detection off
Yellow or yellow flashing 1 x two-channel
Flickering yellow
Configuration mode: Special configuration, two-hand operation
Flickering red
Configuration mode: impermissible configuration
(3) IN
Off
2 x single-channel
Yellow or yellow flashing Startup testing off
(4) SF
Off
Startup testing ON
12.3
Error statuses
LED
Display
Explanation
(1) DEVICE
Red
Device error
Red
Group error
(4) SF
Red flashing
Fault message
12.4
Diagnostics
Power-up
Explanation
DEVICE
OUT
IN
SF
Hardware test
(Note: input expansions remain in this state until
acknowledged by the device on the right-hand side)
Green
Green
Green
Green
The SET/RESET button is stuck, or has been pressed too
long. The device remains in this state until the button is
released again.
Green
flashing
Green
flashing
Green
flashing
Green
flashing
Display of DIP switch configuration
If the DIP switch position is at ON (right), the relevant LED
shows a yellow light
Summary of Contents for SIRIUS 3SK1
Page 2: ......
Page 10: ...Table of contents 3SK1 safety relays 10 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 186: ...Commissioning 3SK1 safety relays 186 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 258: ...Accessories 3SK1 safety relays 258 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 260: ...Appendix A 1 Correction sheet 3SK1 safety relays 260 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 261: ......