Technical data
13.2 Basic units
3SK1 safety relays
200
Manual, 04/2013, A5E02526190021A/RS-AA/01
3SK1111-.AB..
3SK1111-.AW..
Make time
•
with automatic start
– typical
s
0.2
0.11
– for DC maximum
s
0.32
0.13
– for AC maximum
s
0.32
0.13
– after mains power cut
– typical
s
0.2
0.11
– maximum
s
0.32
0.13
•
with monitored start
– typical
s
0.015
– maximum
s
0.02
0.015
Backslide delay time
•
after opening of the safety circuits typical
s
0.01
•
at mains power cut
– typical
s
0.065
0.2
– maximum
s
0.075
0.3
Adjustable backslide delay time
•
after opening of the safety circuits
s
—
Recovery time
•
after opening of the safety circuits typical
s
0.01
•
after mains power cut typical
s
0.09
0.32
Pulse duration
•
of the sensor input minimum
s
0.15
•
of the ON pushbutton input minimum
s
0.015
•
of the cascading-entrance minimum
s
—
Type of voltage of the controlled supply voltage
AC/DC
Control supply voltage frequency
•
1 rated value
Hz
50
•
2 rated value
Hz
60