3SK1 devices
5.1 3SK1 standard
3SK1 safety relays
54
Manual, 04/2013, A5E02526190021A/RS-AA/01
5.1.4.8
Function setting
Table 5- 1
DIP switch
Switch position: left Schematic
DIP switch
No.
Switch position: right
Autostart
1
Monitored start
Cross-circuit detection deactivated
2
Cross-circuit detection activated
2 x single-channel sensor connection
3
1 x two-channel sensor connection
Start-up test ON
1
2
3
4
4
Start-up test OFF
In the delivery state, all the DIP switches are in switch position: right.
Table 5- 2
SET/RESET button
Function of the
SET/RESET button
Status of the indicating LEDs
Function
SET
"DEVICE" LED flashing yellow
•
Press key for about 1 s
The parameterization is loaded
"DEVICE" LED red
"DEVICE" LED flashing green yellow
RESET
"SF" LED red
•
Press key for about 1 s
=> The device restarts without the supply voltage
having to be switched off
Note
The SET/RESET pushbutton only triggers a reset for the device on which the button is
pressed.