3SK1 safety relays
Manual, 04/2013, A5E02526190021A/RS-AA/01
187
Display and diagnostics
12
12.1
LED display
The LED indications of the Advanced safety relays are shown in the tables below. You can
find the LED indications of the Standard safety relays in the chapter "Display of the operating
state (Page 47)".
LED
Display
Explanation
OFF*
No voltage, group error
Configuration mode DIP (1) position: left
Green
Device is ready for operation
Power-up: hardware test
Green flashing
Missing startup testing
Short-circuit on the SET/RESET button
Yellow
Power-up DIP (1) position: right
Yellow flashing
Configuration mode DIP (1) position: right
Green/yellow flashing
Configuration changed
(1) DEVICE
Red
Device error
OFF*
Output inactive
Configuration mode DIP (2) position: left
Green
Output active
Power-up: hardware test
Green flashing
Feedback circuit error
Short-circuit on the SET/RESET button
Yellow
Power-up DIP (2) position: right
Yellow flashing
Configuration mode DIP (2) position: right
START button pressed too long
(2) OUT
Green/yellow flashing
Instantaneous outputs inactive, delayed outputs active