Technical data
13.3 Expansion modules
3SK1 safety relays
Manual, 04/2013, A5E02526190021A/RS-AA/01
233
13.3.1.2
Technical data for output expansion 3SK1213
3SK1213-.AB..
3SK1213-.AJ..
3SK1213-.AL..
Insulation voltage rated value
V
300
Resistance against shock
5 g / 10 ms
Number of sensor inputs 1-channel
or 2-channel
—
Type of the safety-related wiring of
the inputs
—
Product feature transverse contact-
secure
—
Safety Integrity Level (SIL)
according to IEC 61508
SIL3
SIL claim limit (for a subsystem)
according to EN 62061
3
Performance level (PL) according to
ISO 13849-1
e
Category according to ISO 13849-1
4
T1 value for proof test interval or
service life according to IEC 61508
a
20
Safety device type according to
IEC 61508-2
Type A
Number of outputs as contact-
affected switching element
•
as NC contact for reporting
function instantaneous switching
0
•
as NO contact for reporting
function instantaneous switching
0
•
as NC contact for reporting
function delayed switching
0
•
as NO contact for reporting
function delayed switching
0
•
as NC contact safety-related
instantaneous switching
0
•
as NO contact safety-related
instantaneous switching
3
•
as NC contact safety-related
delayed switching
0
•
as NO contact safety-related
delayed switching
0
Stop category according to
DIN EN 60204-1
0
Design of the input start input
—
Design of the electrical connection
jumper socket
No
Summary of Contents for SIRIUS 3SK1
Page 2: ......
Page 10: ...Table of contents 3SK1 safety relays 10 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 186: ...Commissioning 3SK1 safety relays 186 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 258: ...Accessories 3SK1 safety relays 258 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 260: ...Appendix A 1 Correction sheet 3SK1 safety relays 260 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 261: ......