Operation
8.3 LEDs, keys and their meanings (undelayed)
3TK2826 safety relay
Manual, 08/2007, GWA NEB 926 1579-02 DS 02
21
8.3
LEDs, keys and their meanings (undelayed)
Table 8-3
LEDs - undelayed enabling circuits
LED
Status
Meaning
Off
No / too low supply voltage or internal fuse tripped.
Green
Supply voltage in the permissible operating range
Flashing
green
Self-test during restart
Yellow
Configuration mode
Flashing
yellow
Configuration error → change and enable configuration
Device
Red
Device defective → Replace device
Device faulty (e.g. due to electromagnetic interference)→ Press Reset
Off
Output passive
Green
Output active
OUT
Flashing
green
RF not closed while start condition satisfied
Off
Input passive (or switch-on condition not satisfied)
Green
Input active
IN
Flashing
green
Cross-circuit at the input, simultaneity of sensors not satisfied, wire breakage during safety
shutdown mat operation, short circuit to chassis at T1/T2
Off
No group fault
Red
Group fault (wiring fault, cross-circuit, wire breakage in the case of safety shutdown operation,
configuration error) → Eliminate the fault and press Reset
SF
Flashing red
Group fault (RF fault, simultaneity condition of the sensors not satisfied)
Off
Cross-circuit detection off
Yellow
Cross-circuit detection on
1
Flashing
yellow
Configuration mode, waiting for confirmation
Off
NC contact / NO contact
Yellow
NC contact/NC contact
2
Flashing
yellow
Configuration mode, waiting for confirmation
Off
2 x 1-channel
Yellow
1 x 2-channel
3
Flashing
yellow
Configuration mode, waiting for confirmation
Off
Debounce time Y12, Y22, Y34 ~ 50 ms
Yellow
Debounce time Y12, Y22, Y34 ~ 10 ms
4
Flashing
yellow
Configuration mode, waiting for confirmation
Off
Autostart sensor circuit
Yellow
Monitored start sensor circuit
5
Flashing
yellow
Configuration mode, waiting for confirmation