Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
203
Detailed information about the individual data sets can be found in Section Data sets SITOP
Reading and writing data sets SITOP BUF8600
SITOP BUF8600 100 ms/40 A and SITOP BUF8600 300 ms/40 A
Index
Slot
Subslot Data set
Description
Data size
0x0006 1-6
1
Device information
Reading
Information about the buffer compo-
nents SITOP BUF8600.
42 bytes
0x0020 1-6
1
State information
Reading
Status information about the buffer
components SITOP BUF8600.
14 bytes
SITOP BUF8600 4 s/40 A and SITOP BUF8600 10 s/40 A
Index
Slot
Subslot Data set
Description
Data size
0x0006 1-6
1
Device information
Reading
Information about the buffer compo-
nents SITOP BUF8600.
42 bytes
0x0020 1-6
1
State information
Reading
Status information about the buffer
components SITOP BUF8600.
16 bytes
Detailed information about the individual data sets can be found in Section Data sets SITOP
7.6.2.2
Data sets SITOP PSU8600
Index 1: General (reading/writing)
Data
Description
Data type
Priority buffered
Channel 1 (0/255)
Prioritized buffering of output 1 When the power fails, output 1 of the basic
device can be prioritized to increase the available buffer time. In order that the
remaining buffer energy is only used for output 1, in buffer operation, all of the
additional outputs of the power supply system are shut down after half of the
nominal buffer time that is available. When the line supply is available, the
outputs that have been shut down are automatically switched-on again.
Unsigned8
Startup mode
System start characteris-
tics: Defines the time
delay when switching on
the outputs after the de-
vice has powered up. For
a defined switch-on delay
time, the outputs are
switched on in a fixed
sequence 1, 2,… n with
an identical delay time
between the outputs. For
a variable switch-on de-
lay, each output uses an
0 = StartupDelayOff
No on delay
Unsigned8
1 = StartupDelay25 ms 25 ms on delay Outputs
are switched on in an
ascending sequence
(starting with output 1 of
the basic device) in inter-
vals of 25 ms.
2 = StartupDelay
100ms
100 ms switch on delay
Outputs are switched on
in an ascending sequence
(starting with output 1 of
the basic device) in inter-
vals of 100 ms.
Summary of Contents for SITOP BUF8600
Page 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Page 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Page 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Page 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...