Technical data
6.1 Input
SITOP PSU100C
28
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1332-5BA00
(24 V/2.5 A)
6EP1332-5BA20
(24 V/3.7 A)
6EP1332-5BA10
(24 V/4 A)
Input
1-phase AC or DC
Rated voltage
U
e rated / for
AC
100...230 V
Voltage range / for AC
85...264 V
Rated voltage Ue rated / for
DC
120...230 V
Voltage range / for DC
110…300 V
Wide-range input
Yes
Overvoltage strength
2.3 x Ue rated, 1.3 ms
Power failure buffering
at Ia rated, min.
20 ms
Power failure buffering
at Ue = 230 V
Rated line frequency
50/60 Hz
Line frequency range
47...63 Hz
Input current / at rated value
of input voltage 100 V/rated
value
1.21 A
1.88 A
2.25 A
Input current / at rated value
of input voltage 230 V
0.67 A
0.95 A
1.15 A
Inrush current limiting
(+ 25 °C), max.
31 A
30 A
34 A
I²t, max.
2.4 A²·s
3 A²·s
3 A²·s
Integrated input fuse
Internal
Protection in the line feeder
cable (IEC 898)
Recommended miniature circuit-breaker: Characteristic B from 16 A and higher or
characteristic C from 10 A
,QSXWYROWDJH
2XWSXWYROWDJH
%XIIHUWLPH
Figure 6-1
Power failure buffering