Ambient conditions
8
6EP1332-1LB00 (24 V/2.5 A)
6EP1333-1LB00 (24 V/5 A)
6EP1334-1LB00 (24 V/10 A)
6EP1336-1LB00 (24 V/20 A)
Ambient temperature
0 … 60 °C for natural convection (self
convection)
0 … 70 °C for natural convection (self
convection)
Tested according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-78 humid heat, constant
•
EN 60068-2-14 temperature change
Transport and storage temperature
-40 … 85 °C
Tests (packed for shipping) according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, without condensation
Degree of pollution
2
Mechanical stressing in operation
Tested according to:
•
EN 60068-2-6 Vibration, test Fc:
3.5 mm deflection in the range 5 – 8.4 Hz
2 g acceleration in the range 8.4 – 150 Hz
•
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms