Safety, approvals, EMC
7.2 Test voltage
SITOP PSU300S
48
Manual, 12.2016, C98130-A7587-A1-7-7629
7.2
Test voltage
Figure 7-1
Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
●
Connect the input terminals with one another
●
Connect the output terminals, signaling contact and PE with one another
Test (C)
●
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1
Test voltage
Test time
Prim ↔ sec (A)
Prim ↔
PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 V DC
2200 V DC
700 V DC
60 s
3000 V AC
1500 V AC
500 V AC
Production test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Field test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Remark:
Tripping current for DC measurement: 0 mA