FEC920: USER GUIDE
Page 177
September 18
Parameter path
Description
Type
Hex
Dec
Resolution
VirtualChannel.24.Main.Reset
Initiate reset. 0 = No; 1 = Yes
bool
258b
9611
Not applicable
VirtualChannel.24.Main.Resolution
Specifies the resolution/number of decimal places
uint8
2582
9602
Not applicable
VirtualChannel.24.Main.Rollover
A pulse signal to indicate PV (output) has just rolled over
bool
2591
9617
Not applicable
VirtualChannel.24.Main.RolloverValue
Rollover value
float32
2592
9618
Set by VirtualChannel.24.Main.Resolution
VirtualChannel.24.Main.Status
As VirtualChannel1.Main.Status
uint8
016d
365
Not applicable
VirtualChannel.24.Main.TimeRemaining
Time remaining before the calculation is made
time_t
2589
9609
Set by Network.Modbus.TimeFormat
VirtualChannel.24.Main.Trigger
Increment/decrement counter. 0 = No; 1 = Yes
bool
258e
9614
Not applicable
VirtualChannel.24.Main.Type
As VirtualChannel1.Main.Type
uint8
2580
9600
Not applicable
VirtualChannel.24.Main.Units
Units descriptor
string_t
4d83
19843
Not applicable
VirtualChannel.24.Main.UnitsScaler
Units scaler for totalisers
float32
2583
9603
1dp
VirtualChannel.24.Trend.Colour
As VirtualChannel1.Trend.Colour
uint8
26a0
9888
Not applicable
VirtualChannel.24.Trend.SpanHigh
Specifies the highest PV (output value) to be displayed
float32
26a2
9890
Same as VirtualChannel.24.Main.PV
VirtualChannel.24.Trend.SpanLow
Specifies the lowest PV (output value) to be displayed
float32
26a1
9889
Same as VirtualChannel.24.Main.PV
VirtualChannel.25.Main.Descriptor
Virtual Channel descriptor
string_t
4d89
19849
Not applicable
VirtualChannel.25.Main.Disable
1 = Virtual channel disabled
bool
26e3
9955
Not applicable
VirtualChannel.25.Main.HighCutOff
The highest input value that will be totalised/counted
float32
25c5
9669
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.Input1
Input 1 value
float32
25c7
9671
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.Input2
Input 2 value
float32
25c8
9672
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.LowCutOff
The lowest input value that will be totalised/counted
float32
25c4
9668
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.ModbusInput
Modbus input value
float32
25c6
9670
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.Operation
Specifies the operation of the virtual channel
uint8
25c1
9665
Not applicable
VirtualChannel.25.Main.Period
The time period over which the calculation is made
int32
25ca
9674
Not applicable
VirtualChannel.25.Main.Preset
Initiate preset. 0 = No; 1 = Yes
bool
25cc
9676
Not applicable
VirtualChannel.25.Main.PresetValue
Specifies the preset value
float32
25cd
9677
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.PV
The virtual channel output value
float32
016e
366
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.Reset
Initiate reset. 0 = No; 1 = Yes
bool
25cb
9675
Not applicable
VirtualChannel.25.Main.Resolution
Specifies the resolution/number of decimal places
uint8
25c2
9666
Not applicable
VirtualChannel.25.Main.Rollover
A pulse signal to indicate PV (output) has just rolled over
bool
25d1
9681
Not applicable
VirtualChannel.25.Main.RolloverValue
Rollover value
float32
25d2
9682
Set by VirtualChannel.25.Main.Resolution
VirtualChannel.25.Main.Status
As VirtualChannel1.Main.Status
uint8
016f
367
Not applicable
VirtualChannel.25.Main.TimeRemaining
Time remaining before the calculation is made
time_t
25c9
9673
Set by Network.Modbus.TimeFormat
VirtualChannel.25.Main.Trigger
Increment/decrement counter. 0 = No; 1 = Yes
bool
25ce
9678
Not applicable
VirtualChannel.25.Main.Type
As VirtualChannel1.Main.Type
uint8
25c0
9664
Not applicable
VirtualChannel.25.Main.Units
Units descriptor
string_t
4d9e
19870
Not applicable
VirtualChannel.25.Main.UnitsScaler
Units scaler for totalisers
float32
25c3
9667
1dp
VirtualChannel.25.Trend.Colour
As VirtualChannel1.Trend.Colour
uint8
26e0
9952
Not applicable
VirtualChannel.25.Trend.SpanHigh
Specifies the highest PV (output value) to be displayed
float32
26e2
9954
Same as VirtualChannel.25.Main.PV
VirtualChannel.25.Trend.SpanLow
Specifies the lowest PV (output value) to be displayed
float32
26e1
9953
Same as VirtualChannel.25.Main.PV
VirtualChannel.26.Main.Descriptor
Virtual Channel descriptor
string_t
4da4
19876
Not applicable
VirtualChannel.26.Main.Disable
1 = Virtual channel disabled
bool
2723
10019
Not applicable
VirtualChannel.26.Main.HighCutOff
The highest input value that will be totalised/counted
float32
2605
9733
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.Input1
Input 1 value
float32
2607
9735
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.Input2
Input 2 value
float32
2608
9736
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.LowCutOff
The lowest input value that will be totalised/counted
float32
2604
9732
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.ModbusInput
Modbus input value
float32
2606
9734
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.Operation
Specifies the operation of the virtual channel
uint8
2601
9729
Not applicable
VirtualChannel.26.Main.Period
The time period over which the calculation is made
int32
260a
9738
Not applicable
VirtualChannel.26.Main.Preset
Initiate preset. 0 = No; 1 = Yes
bool
260c
9740
Not applicable
VirtualChannel.26.Main.PresetValue
Specifies the preset value
float32
260d
9741
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.PV
The virtual channel output value
float32
0170
368
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.Reset
Initiate reset. 0 = No; 1 = Yes
bool
260b
9739
Not applicable
VirtualChannel.26.Main.Resolution
Specifies the resolution/number of decimal places
uint8
2602
9730
Not applicable
VirtualChannel.26.Main.Rollover
A pulse signal to indicate PV (output) has just rolled over
bool
2611
9745
Not applicable
VirtualChannel.26.Main.RolloverValue
Rollover value
float32
2612
9746
Set by VirtualChannel.26.Main.Resolution
VirtualChannel.26.Main.Status
As VirtualChannel1.Main.Status
uint8
0171
369
Not applicable
VirtualChannel.26.Main.TimeRemaining
Time remaining before the calculation is made
time_t
2609
9737
Set by Network.Modbus.TimeFormat
VirtualChannel.26.Main.Trigger
Increment/decrement counter. 0 = No; 1 = Yes
bool
260e
9742
Not applicable
VirtualChannel.26.Main.Type
As VirtualChannel1.Main.Type
uint8
2600
9728
Not applicable
VirtualChannel.26.Main.Units
Units descriptor
string_t
4db9
19897
Not applicable
VirtualChannel.26.Main.UnitsScaler
Units scaler for totalisers
float32
2603
9731
1dp
VirtualChannel.26.Trend.Colour
As VirtualChannel1.Trend.Colour
uint8
2720
10016
Not applicable
VirtualChannel.26.Trend.SpanHigh
Specifies the highest PV (output value) to be displayed
float32
2722
10018
Same as VirtualChannel.26.Main.PV
VirtualChannel.26.Trend.SpanLow
Specifies the lowest PV (output value) to be displayed
float32
2721
10017
Same as VirtualChannel.26.Main.PV
VirtualChannel.27.Main.Descriptor
Virtual Channel descriptor
string_t
4dbf
19903
Not applicable
VirtualChannel.27.Main.Disable
1 = Virtual channel disabled
bool
2763
10083
Not applicable
VirtualChannel.27.Main.HighCutOff
The highest input value that will be totalised/counted
float32
2645
9797
Set by VirtualChannel.27.Main.Resolution
VirtualChannel.27.Main.Input1
Input 1 value
float32
2647
9799
Set by VirtualChannel.27.Main.Resolution
VirtualChannel.27.Main.Input2
Input 2 value
float32
2648
9800
Set by VirtualChannel.27.Main.Resolution
VirtualChannel.27.Main.LowCutOff
The lowest input value that will be totalised/counted
float32
2644
9796
Set by VirtualChannel.27.Main.Resolution
VirtualChannel.27.Main.ModbusInput
Modbus input value
float32
2646
9798
Set by VirtualChannel.27.Main.Resolution
VirtualChannel.27.Main.Operation
Specifies the operation of the virtual channel
uint8
2641
9793
Not applicable
VirtualChannel.27.Main.Period
The time period over which the calculation is made
int32
264a
9802
Not applicable
VirtualChannel.27.Main.Preset
Initiate preset. 0 = No; 1 = Yes
bool
264c
9804
Not applicable
VirtualChannel.27.Main.PresetValue
Specifies the preset value
float32
264d
9805
Set by VirtualChannel.27.Main.Resolution
VirtualChannel.27.Main.PV
The virtual channel output value
float32
0172
370
Set by VirtualChannel.27.Main.Resolution
VirtualChannel.27.Main.Reset
Initiate reset. 0 = No; 1 = Yes
bool
264b
9803
Not applicable
VirtualChannel.27.Main.Resolution
Specifies the resolution/number of decimal places
uint8
2642
9794
Not applicable
VirtualChannel.27.Main.Rollover
A pulse signal to indicate PV (output) has just rolled over
bool
2651
9809
Not applicable