Operating instruction A5E02591611-02
7.2 Settings
Line Fault detection LF
Deactivated *
Activated
*) Default factory setting
Please note: The line fault detection is applied for the input and output circuits. The line
fault detection monitors the common input channel and the according output channel. An
open output (without load) leads to fault indication. Please connect a load of 250 Ohm to
the unused output.
The DIP switch settings may be changed during operation in Zone 2 as well and in the
case of connected, intrinsically safe input signals.
LF1
ON
OFF
1
LF1
ON
OFF
1