Page 102
SITRANS LC500 – OPERATING INSTRUCTIONS
7ML19985GE04
Appendix E
Larger tank, dimensions in feet:
Application: level indicator and solid-state switch output
The loop current provides:
•
a reading proportional to level, within the 0 - 100% range, at menu 00 or 10 on the
device, or at a remote indicator
•
an out-of-range signal ooL alternating with PV if the level is above URV or below
LRV
The solid-state switch is activated at Upper Threshold Setting and deactivated at Lower
Threshold Setting. In the diagram below, it is used to activate a pump via an auxiliary
power circuit.
•
The activation and deactivation can be modified by Upper and/or Lower Threshold
delays (menus 13 and 14).
•
The reading can be stabilized if necessary by applying Damping (menu 0A): the
update value for Damping is controlled by menu 09.
Example:
The level is to be held between 90% and 8%.
For this slightly larger tank, the capacitance
ranges from 16.6 pF for 0% (probe in air) to 33.2 pF
for 100% (tank filled with oil).
After calibration:
16.6 pF
0%
4 mA or 20 mA
33.2 pF
100%
20 mA or 4 mA
Cair
air
7.32
4.5
Log
60 0.63
-----------------------------------
pF
16.6
pF
=
=
Coil
oil
7.32
4.5
Log
60 0.63
-----------------------------------
pF
33.2
pF
=
=
SITRANS
LC500
6” (0.5ft)
L = 54”
(4.5ft)
60”
(5.0ft)
d = 0.63”
P
Indicator: primary variable viewed at menus 00 or 01;
units or% selected in menu 01
0-100%
auxiliary
power
pump
power
solid-
state
output
current loop connection
(menu 0F) URV = 100%
Upper Threshold Setting = 90%
menu 15 (activation hysteresis)
menu 16 (deactivation hysteresis)
Lower Threshold Setting = 8%
(menu 0E) LRV = 0%
(menu 0C) USL
(menu 0B) LSL
solid-state
switch
output:
selected at
menu 17
and
controlled
by menus
13 to 18.
75.8 pF
14.3 pF
Active shield section